It not only meets the test requirements of excitation characteristics (i.e. volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary load, ratio difference, and angle difference of various CTs (such as: protection, metering, TP), but also can be used for excitation characteristics, ratio, polarity, and secondary winding resistance tests of various PT electromagnetic units.
On-site verification of current transformers does not require standard current transformers, current boosters, load boxes, voltage control boxes, and high-current wires. Simple test wiring and operation are used to realize the verification of current transformers, which reduces the work intensity and improves the work efficiency, and facilitates on-site verification of transformers; fast, simple, accurate, and convenient.
Technical indicators | |
Test purpose | protection and metering CT, protection PT |
Input power supply | voltage AC220V±10%; frequency 50/60Hz |
Output voltage | 0~180Vrms, current 12Arms, 36A (peak) |
CT ratio | measurement range 1~40000; accuracy ±0.2% |
PT ratio | measurement range 1~40000; accuracy ±0.5% |
Phase measurement | accuracy ±3min; resolution 0.3min |
AC load measurement | range 0~300VA; resolution 0.01VA; accuracy 0.5%±0.1VA |
Working conditions | ambient temperature 0~40ºC, humidity: ≤75% RH |
Diameter | 340mm×296mm×174mm |
Weight | 9kg |
Environmental conditions | operating temperature -10ºC~+50ºC; storage temperature -10ºC~+50ºC; humidity Relative humidity: 5% to 95%, no condensation |
Secondary winding resistance measurement | range 0~300Ω; resolution 1mΩ; accuracy 3%±1mΩ AC load measurement: range 0~300VA; resolution 0.01VA; accuracy 0.5%±0.1VA |