- Electronic housing is made of aluminum alloy, and the housing protection level is IP66
- Reverse polarity protection and instantaneous overcurrent and overvoltage protection measures, strong anti-interference, and good long-term stability
- High precision and good stability
- Reliable circuit and fast response speed
| Measuring Temperature Range | -196…0~100…1500ºC |
| Measuring Medium | various liquid, gas, or steam compatible with 304 or 316L stainless steel |
| Sensor | PT100, thermocouple, etc. |
| Accuracy | ±0.5%FS |
| Long-term Stability | ±0.2%FS/year |
| Insertion Depth | customization |
| Installment Thread | customization |
| Operation Temperature | -40~85ºC(Normal model); -40~60ºC(Explosion-proof model) |
| Storage Temperature | -40~85ºC |
| Supply Voltage | DC12~28V (Normal model). DC12~26V (Explosion-proof model) |
| Output Signal | 2-wire 4~20mADC,or RS485, switch signal etc |
| Allowable load resistance | 0~600Ω(DC 24V, including cable resistance) |
| Protection Grade | IP65 |
| Electrical Connection | Cables with cable gland |
| Working environment humidity | no more than 90% (+25ºC) |
| Working altitude | no more than 2000m |
| Working atmospheric pressure | 86~106Kpa |
| Explosion-proof | Ex db IIC T6 Gb Ex tb IIIC T80ºC Db
|


| Model | Type | ||||||||
| HTM208 | HTM208 digital temperature transmitter | ||||||||
| Code | Installation | ||||||||
| LW-G | Threaded installation | ||||||||
| FL-G | Flange installation | ||||||||
| KP | Clamp installation | ||||||||
| Range | Measuring Range | ||||||||
| (0~X) ºC | Fill X directly | ||||||||
| Code | Output singnal | ||||||||
| B1 | (4~20)mA | ||||||||
| B7 | RS485 | ||||||||
| B8 | HART | ||||||||
| code | Installation form | ||||||||
| 1 | Fixed | ||||||||
| 2 | Movable | ||||||||
| Code | Process Connection | ||||||||
| P1 | M20×1.5 | ||||||||
| P4 | G1/2 | ||||||||
| P17 | M27×2 | ||||||||
| P22 | M16×1.5 | ||||||||
| K1 | 1.5'' clamp | ||||||||
| K2 | 2'' clamp | ||||||||
| F20 | DN20 | ||||||||
| F50 | DN50 | ||||||||
| Code | Electronical Connection | ||||||||
| C2 | Cable | ||||||||
| Code | Sensor type | ||||||||
| P | PT100 | ||||||||
| K | K index thermocouple | ||||||||
| S | S index thermocouple | ||||||||
| Code | Others | ||||||||
| d | Exd IIC T6 Gb | ||||||||
| f | Ex tb IIIC T80ºC Db | ||||||||
| l | l=insertion depth(mm) | ||||||||
| L | L=Total length of protective tube(mm) | ||||||||
| ϕ | ϕ=Protection tube diameter(mm) | ||||||||
| F | Special anti-corrosion requirements | ||||||||
| HTM208 | LW-G | (0~300) ºC | B1 | 1 | P1 | C2 | P | d l=200 L=350 ϕ=12 | |

| HTM128 Explosion proof temperature transmitter Ex db IIC T6 Gb | HPM81 Explosion proof pressure transmitter Ex ia II C T4 Ga Ex d II C T4~T6 Gb Ex tb IIIC T85ºC...T135ºC Db |
![]() | ![]() |



1. Q: Are you manufacturer or trading company?
A: We are manufacturer which focuses on sensor for 10 years.
2. Q: What's your quality control system?
A: MC, ISO9001, CE Certificated.
3. Q: What is the warranty of your products?
A: Our warranty time is 18 months after shipment.
A: We could accept T/T, Paypal, WU.








Audited Supplier