| * GMCC Compressor with R410A; |
| * High efficiency hydrophilic aluminum foil fin heat exchanger; |
| * "SANHUA" EEV; |
| * "Lifeng" fan ; |
| * Delivery time:about 30days after received deposit; |
| * Payment:T/T 30% prepaid ,then pay for the balance before delivery; |
| *Package:ply-wood cases; |
| * Warrenty:18month; |
WE SUPPLY OEM SERVICE!
KONNEN NEW FACTORY(HEAT PUMP + WATER TANK + CONTROLLER):
KONNEN AIR SOURCE HEAT PUMP, AIR TO WATER HEAT PUMP, COMMERCIAL USE:| * Panasonic compressor & R410a refrigerant, OR Copeland compressor and R417a refrigerant; |
| * Stainless steel 304 for all fasteners, for side covers of evaporator; |
| * Preservative oil for copper tubes and all important part of cabinet; |
| * Chinese No.1 brand "ND" shell & tube heat exchanger; |
| * Japan "Saginomiya" or "Sanhua" electronic expansion valve; |
| * "Sanhua" 4-way valve; |
| * "Schneider" AC contactor & Relay |
| * LCD controller; |
| * Delivery time: 20~25 days; |
| * Payment term: T/T 30% in advance and T/T 70% before delivery; |
| * Warranty time: 24 months after delivery. |
WE SUPPLY OEM SERVICE!
KONNEN NEW FACTORY(HEAT PUMP + WATER TANK + CONTROLLER):

WHY US:

KONNEN NEW PROJECTS:

WORLD FAMOUS BRANDS WE COOPERATED FOR OUR HEAT PUMPS:

KONNEN HEAT PUMPS LOADING:

PARAMETERS TABLE:
| Model | RF8I/bd | RF12/bd | RF16I/bd | |
| Power Supply V/Ph/Hz | 220/1/50 | |||
| Rated Current Input Without E-heater (A) | 20 | 24 | 30 | |
| Rated Condition 7ºC | Heating Capacity (KW) | 8.8 | 12 | 17 |
| Power Input (KW) | 2.55 | 3.55 | 4.91 | |
| COP | 3.45 | 3.4 | 3.5 | |
| Nominal Condition -12ºC | Heating Capacity (KW) | 5.41 | 10.50 | 12.13 |
| Power Input (KW) | 2.25 | 4.40 | 5.05 | |
| COP | 2.40 | 2.40 | 2.40 | |
| Low Temp. Condition -20ºC | Heating Capacity (KW) | 4.78 | 9.21 | 10.52 |
| Power Input (KW) | 2.45 | 4.56 | 5.18 | |
| COP | 1.95 | 2.02 | 2.03 | |
| Low Temp. Condition -25ºC/Water output temp. 41ºC | Heating Capacity (KW) | 3.55 | 6.82 | 7.80 |
| Power Input (KW) | 2.20 | 4.21 | 4.81 | |
| COP | 1.61 | 1.62 | 1.62 | |
| Low Temp. Condition -25ºC/Water output temp. 50ºC | Heating Capacity (KW) | 3.19 | 6.14 | 7.02 |
| Power Input (KW) | 2.28 | 4.23 | 4.91 | |
| COP | 1.40 | 1.42 | 1.43 | |
| Rated Cooling Condition | Cooling capacity (KW) | 8.00 | 11.50 | 12.00 |
| Power input (KW) | 3.20 | 4.60 | 4.80 | |
| EER | 2.50 | 2.50 | 2.50 | |
| Max. Water Output Temp. Under Ambient Temp. -25ºC | 56.2ºC | 56.1ºC | 56.2ºC | |
| Noise Level dB(A) | 59.5 | 60.5 | 61.5 | |
| Refrigerant | R410A | R410A | R410A | |
| Water Flow | 1.38 m³/h | 1.92 m³/h | 2.67 m³/h | |
| Pipe Size | DN20 | DN25 | DN25 | |
| Dimensions | 947*403*813mm | 940*393*1373mm | 940*393*1373mm | |
| Net Weight | 80Kg | 110kg | 110kg | |
| Testing Condition: - Rated condition: Inlet/outlet temperature 40°C/45°C. Dry bulb/wet bulb temperature 7°C/6°C - Nominal condition: Outlet temperature 41°C. Dry bulb/wet bulb temperature -12°C/-14°C - Low temperature condition: Outlet temperature 41°C. Dry bulb/wet bulb temperature -20°C/-21°C - Rated cooling: Inlet/outlet temperature 12°C/7°C. Dry bulb/wet bulb temperature 35°C/24°C - Internal and external machine connection copper pipe are 5m. If need for exceeds 7.5m, you need to contact the manufacturer to change the amount of refrigerant. | ||||

heat pump,air source heat pump,air to water heat pump,swimming pool heat pump,water to water heat pump,ground soruce heat pump,DC inverter heat pump,water source heat pump








Audited Supplier