which are energized. The disconnectors do not have any inductive devices and are therefore intended for switching on and off electrical circuits in the absence of load current.
- pre-shipment setup and adjustment;
- accurate actuator settings without disassembly;
- MGB lock mounting bracket with the possibility to install a ZB type lock; - increased corrosion resistance of the contact knives;
- special packaging to prevent condensation and rust.
Contact breaker system with visible circuit breakage.
Mechanical interlocking of the actuators.
Current-carrying elements made of high-quality M1 copper.
Built-in, welded construction of the disconnector made of high-quality M1 copper.
Built-up, welded construction of the disconnector.
Wide range of versions: rated current, number of poles, and position of earthing legs.



Parameter name | Significance |
| Number of poles | 1, 3 |
| Rated voltage, Unom/Unr, kV | 10/12 |
| Rated current, Inom, A | 400, 630, 1000 |
| Thermal resistance limit current, It, kA | 400 А - 16 630 А - 20 1000 А - 31,5 |
The current of electrodynamic withstand, Id, kA | 400 А - 41 630 А - 52 1000 А - 80 |
| Electrical resistance of the main circuit of the loop, Ohm | 104х10-6 |
| Nominal frequency, Hz | 50/60 |
| Climatic version | U3, UHL2 |
| Degree of protection | IP00 |












Audited Supplier