Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source

Price $80000.00
Min Order 1 Piece
Availability In Stock
Shipping From Hunan, China
Popularity 391 people viewed
Model NO.:
TH3600
After-sales Service:
24 Hours
Warranty:
1 year
Application:
Electromagnetic Instrument, Electrical Calibrator
Power:
Electricity
LCD Display:
With LCD Display
Customized:
Non-Customized
Accuracy Class:
0.005 (50 ppm) / 0.01(100 ppm)
Maximum Voltage Output:
528 V
Maximum Current Output:
120 mA
Minimum current output:
20μA
Harmonic function (optional):
2nd to 63rd
Power Supply:
AC ( 220 ± 22 ) V, ( 50 ± 2 ) Hz
Communication Interface:
RS232, LAN
Trademark:
TUNKIA
Transport Package:
Package for Exporting
Origin:
China
Product Description
 
TH3600 Broadband Low Current Standard Power Source
 
1.Summary

TH3600 is a three-phase standard power source with wide frequency and low current output. The output bandwidth is 45 Hz~1kHz, and the low current output can be as low as 20μA. It can be used as a power/energy calibration source for high-precision current measurement and analysis below 120mA. It makes up for the serious shortcomings of traditional electric energy meter calibration devices in broadband and low current measurement. It has optional power accuracy of class 0.005 and 0.01.

2.Features
  1. Maximum output: 528 V / 120 mA, which can ensure the stability of value output under full load conditions.
  2. Minimum current output: as low as 20μA.
  3. Multi-functional electric energy measurement: It has forward, reverse active and reactive energy, and supports the calibration of electric energy meters.
  4. Harmonic function (optional): Can load 2nd to 63rd harmonics with adjustable amplitude and phase to complete the harmonic impact test.
3. Specification

3.1 ACV Output

RangeResolutionLoad CapacityShort-term Stability 
( ppm / min )
Measurement Uncertainty
 ( ppm*RD+ppm*RG,45Hz~65Hz)
Total Harmonic Distortion
(THD, % )
Class 0.005Class 0.01Class 0.005Class 0.01
60 V0.01 mV0.3A51012 + 825 + 15< 0.01
120 V0.1 mV0.15A51012 + 825 + 15< 0.01
240 V0.1 mV0.08A51012 + 825 + 15< 0.01
480 V0.1 mV0.04A51012 + 825 + 15< 0.01
  1. Output range: 6 V ~ 528 V, 7-digit display
  2. Adjustment fineness: 3ppm
  3. Protection functions: short circuit protection, overload protection, temperature protection
 

3.2 ACI Output

RangeResolutionLoad CapacityShort-term Stability
( ppm / min )
Measurement Uncertainty 
 ( ppm*RD+ppm*RG,45Hz~65Hz)
Total Harmonic Distortion
(THD, % )
Class 0.005Class 0.01Class 0.005Class 0.01
0.2 mA0.1 nA8V122030 + 2050 + 30< 0.02
0.5 mA0.1 nA8V122030 + 2050 + 30< 0.02
1 mA1 nA8V81520 + 1030 + 20< 0.02
2 mA1 nA8V81520 + 1030 + 20< 0.01
5 mA1 nA8V81520 + 1030 + 20< 0.01
10 mA10 nA8V81520 + 1030 + 20< 0.01
20 mA10 nA8V81520 + 1030 + 20< 0.01
50 mA10 nA8V81520 + 1030 + 20< 0.01
100 mA100 nA8V81520 + 1030 + 20< 0.01
  1. Output range: 0.02 mA~120 mA, 7-digit display
  2. Adjustment fineness: 3ppm
  3. Protection functions: open circuit protection, overload protection, temperature protection
 

3.3 Frequency / Phase

ParameterAdjustment RangeOptimal Measurement Uncertainty (k=2)
Frequency45.0000 Hz~1000.000 Hz50 ppm*RD
Phase0.000 0°~359.999 9°0.001°
Harmonic (optional)2nd~63rd, amplitude 0~40% (total harmonic distortion does not exceed 50%), phase adjustable from 0.0°~ 359.99°
 

3.4 Power / Energy

Measured PowerVoltage RangeCurrent RangeMeasurement Uncertainty
(45Hz~65Hz,k=2)
Class 0.005Class 0.01
Active Power / Energy
Apparent Power
|cosj| ≥ 0.5
30 V ≤ U ≤ 480 V0.05 mA ≤ I <1 m A0.005%*FS0.01%*FS
1 mA ≤ I < 100 mA0.005%*RD0.01%*RD
Reactive Power
|sinj| ≥ 0.5
30 V ≤ U ≤ 480 V0.05 mA ≤ I <1 m A0.01%*FS0.02%*FS
1 mA ≤ I < 100 mA0.01%*RD0.02%*RD
Power Factor30 V ≤ U ≤ 480 V0.05 mA ≤ I <1 m A0.01%0.02%
1 mA ≤ I < 100 mA0.005%0.01%
Note: FS = voltage range value × current range value
  1. Power/electric energy measurement range: combination of AC voltage range and AC current range
  2. Power factor measurement range: -1.000 00…0.000 00…1.000 00
  3. Standard electric energy pulse output: high frequency full scale value corresponds to 60 kHz, low frequency full scale value corresponds to 6 Hz
  4. Standard power pulse input: frequency ≤ 200 kHz, voltage: 0…3.3 V…24 V
  5. Power error display: automatic, resolution 0.0001%
 
4.General Specification
Power SupplyAC ( 220 ± 22 ) V, ( 50 ± 2 ) Hz
Preheat Time30mins
Temperature PerformanceWorking temperature: 15°C~30°C;
Storage temperature: -10°C~55°C
Humidity PerformanceWorking humidity: < 80% @ 30°C, < 70% @ 40°C, < 40% @ 50°C
Storage humidity: (20%~80%) R·H, non-condensing
Communication InterfaceRS232,LAN
 

5. Ordering Information




 
Company Profile
 

  • Similar Products
Full Page Contact Supplier