ROTA-100 Smart Pump Controller is designed to control one single phase pump, 220VAC, 50Hz. It is compatible with control signal including
4~20mA, float switches, pressure switch, etc.
It is IP65 protection grade for outdoor or indoor use. All the pump operating status, alarm notification can be viewed without openning the door cover. ROTA-100 is integrated with intelligent PLC, and colorful HMI (7" touch screen); it is with complete pump protection function; On-site system healthy diagnosing, visual & sound alarm notifiction function.
ROTA-100 is easy to use, all of the pump operating data and trend can be viewed through touch screen. With modbus RS485 communication
protocol, ROTA-100 can be communicated with upper computer SCADA system, realize the remote monitoring of the pumping stations in a certain area.


Composition:


Main features:
Backup 4 float switches:
Low level: Pump STOP (ensuring motor submergence)
Back up pressure switch: 24VDC:
brightness: 350 lumens ,
√ Real-time monitoring of the pump system, including
pump running current,
pump starts,
pump running time,
overload event,
over pressure event,
power reset,
lastest alarm information
√ water level bar graph display;
√ System event and trend can be viewed on HMI, including amps, water level, flow,etc;
√ All the alarms status can be read on HMI
Over-temperature protection;
Overflow protection at a 24 hrs period;
Pump run indication
Specification:
Rated Input Voltage: | 240VAC, 50Hz |
Rated current : | 0~10A |
Maximum current: | 40A |
Qty.of Controlled Pump: | One pump |
Level Transmission Type: | •4~20mA Level sensor; •float switches (4pcs) (backup); •Pressure switch; |
Enclosure: | •PC Plastic Enclosure, with clear enclosure cover, •High strength, UV resistance; •Lockable with all locks; •Fitted with non-corrosive hinges and locking latch; |
Protection grade: | IP65 |
Display: | 7" LCD touch screen |
PLC: | 24VDC, I/O: 4 digital input/output; 4 analog input/output; RS485 communication |
Outer Dimension: | 400 ×300 × 220 mm |
Installation: | Wall mounting |
Working temperature: | -25ºC-- +55ºC |
Working humidity: | 20%--90%RH, no drips concreted |
Max.Control Distance: | ≤2000m without strong electric and electromagnetic fields |
Control Function: | •Low Level - Pump stop; •High Level - Pump start; •Low Low Level - Pump stop, and dry run protection alarm will be triggered; •High High Level - Pump start, and high level alarm will be triggered; •Pressure monitoring - Pump can be turned off when high pressure alarm triggered; •Pump running time monitoring - when pump running time exceed the maximum time in a period, the system can send the alarm; •Pump start, stop delay time can be set, solve the problems such as liquid level fluctuation and water hammer; •Automatic restart after power recovery etc. |
Protection Function: | •Over-load protection; •Dry run protection; •Short circuit protection; •Over-temperature protection; •Over-pressure protection; •Pump leakage protection; •Over/under-voltage protection; •Over-flow protection |
Data log and storage: | •Pump run indication •Number of high levels •Number of starts (total) •Number of power resets •Number of over current shut-downs •Number of starts per hour •Motor running current •Last motor current •Peak and average current during last run cycle •Level settings record; •Data logging with real-time clock; •Minimum 30 days data storage before it is over-written. |
Alarm notification: | •over-load; •over- temperature; •dry turn; •over-voltage; •over-pressure; •pump excess runtime across a 24hr period; •high level; •4~20mA level transmitter fail; •float switches fail; |